SB167 S H&HR AM #1

Johnson 7909

 


The Committee on  Health and Human Resources  moved to amend the bill on page one, section one, line five, after the word “authorized” by striking out the period and adding the following:  with the following amendment:

One page six, by striking out all of subdivision 8.1. and inserting in lieu thereof a new subdivision 8.1., to read as follows:

8.1. A public water system which artificially adjusts fluoride levels shall strive to maintain those levels between 0.6 milligrams per liter and 0.8 milligrams per liter. The optimum target concentration for artificially adjusted fluoride is 0.7 milligrams per liter. If the drinking water of a public water system is found to be outside of the 0.6 to 0.8 milligrams per liter range, the public water system shall make any treatment or operational changes necessary to return the fluoride level to within the range within 24 hours of receiving the analytical result unless doing so is impracticable, in which case, the correction shall be made as soon as possible. A public water shall identify in its annual report to the Bureau the date and time of each instance where the fluoride levels were found to be outside the target range and how long it took to implement responsive adjustments.


 

 

 

Adopted

Rejected